Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 04/05/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) ENTRANCES ABOVE CURRENT CARING PART? TO HAVE AN APPROVED SEALING DEVICE. 2) TIGHTEN LOOSE FITTINGS. 3) CHASE NIPPLE NOT AN APPROVED FITTING. 4) COVER TO BE WEATHER PROOF WETHER OR NOT PLUGGED IN. 5) SUPPORT CONDUIT AS PER CODE |
| 04/01/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS TO GROUNDED TERMINAL. 2) SLEEVE AND FITTING TO ATTACH TO PANEL. 3) FINISH CIRCUIT RE CONNECTORS. OK TO CLEAR RESIDENTIAL UPGRADE. CALLED TEP MAP ROOM 2:50PM |