Permit: T05EL00511

Parcel: 10706002D

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05EL00511

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/23/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* #1 2010 UNDERGROUND OK TO COVER 2-2" PVC FEEDERS FROM SERVICE ENTRANCE AREA TO PEDESTALS # 106 AN # 156. #2 NOTICE TO OWNER REGARDING THE MAIN SERVICE ENTRANCE SECTION CONSISTING OF 3 HIGH VOLTAGE TRANSFORMERS FEEDING 4-400 AMP DISCONNECTS WHERE TWO 200 AMP MH PEDESTALS ARE CURRENTLY WANTING TO GET SERVICE. THE APPROX 1600 AMP SERVICE IS IN A STATE OF REQUIRING UPGRADE. SECTION 203 OF THE TUCSON CODE, UNIFORM ADMINISTRATIVE CODE ( 1997) STATES WHEN SERVICE EQUIPMENT CONSTITUTES A HAZARD DUE TO DILAPIDATION, OBSOLESCENS, IMPROPER MAINTENACE, OR DETERIORATION-THAT FOR THE PURPOSE OF THIS CODE IT IS AN UNSAFE USE. THE TWO NEW SERVICES CANNOT BE CONNECTED UNTIL SERVICE IS UPGRADED. DUE TO OLD AGE, NON WEATHERPROOF OF EXPOSED PARTS, THIS SERVICE IS IN DIRE NEED OF REPLACEMENT. THE 2002 NATIONAL ELECTRICAL CODE IS ALSO USED TO CITE PROBLEMS AT SERVICE, ALSO THE NEIGHBORHOOD PRESERVATION ORD # 9816-16.14,14 NOTES HAZARDOUS ELECTRICAL WIRING BECAUSE OF OBSOLESCENCE & DILAPIDATION A FIRE HAZARD. OBTAIN THE SERVICES OF AN ELECTRICAL ENGINEER TO REVIEW AND OBTAIN PERMITS FOR A NEW SERVICE.