Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/17/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL ITEMS FROM INFRONT OF MAIN DISCONNECTS.THIS AREA SHOULD ALWAYS BE CLEAR. 2) # 12 WIRE CONNECTED AT EACH SERVICE DISCONNECT NEUTRAL DOES NOT BELONG CONNECTED. INSIDE M-OK. INSIDE L-REJECTED INSIDE PANEL MISSING, RANGE RECEPTACLE MISSINGT, ? SERVICE COVERS MISSING. INSIDE O FUSES MISSING, RANGE FUSES MISSING. INSIDE Q FUSES MISSING RANGE FUSES MISSING. |