Permit: T05EL00493

Parcel: 106030990

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/15/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SERVICE NEEDS PERMANENT ADDRESS ON IT. 2) THE # 10 WIRE FEEDING THE 60AMP DISCONNECT IS TOO SMALL IT SHOULD BE # 6 COPPER. 3) THE JUNCTION BOX BELOW SERVICE SHOULD BE WEATHERPROOF. 4) THE MAIN DISCONNECT PANEL AT UNIT # 2 IS REQUIRED TO HAVE IT'S OWN GROUNDING SYSTEM. 5) THE #6 SE CABLE ENTERING THE PANEL HAS TO BE PHYSICALLY PROTECTED, THE BOTTOM HOLE IN THE PANEL SEALED. 6) REMOVE UNUSED WHTE ?? GREEN WIRE CONNECTED TO NEUTRAL . 7) OUSIDE COOLER NO WIRED. 8) KNOCKED ON DOOR NO ANSWER- NEED TO INSPECT INSIDE TO COMPLETE INSPCTION - ALL RECEPTACLES, SWITCHES LIGHTS AND SMOKE DETECTOR IN BEDROOM. PLEASE HAVE OWNER MAKE CORRECTIONS & RECALL & HAVE OPEN. THIS INSPECTION DOES NOT INCLUDE INSIDE.