Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL BREAKERS WITH PERMANENT MARKER. 2) INSTALL FILLER BLANK AT PANEL 3) ROMEX STAPLES NOT SUITABLE FOR SECURING GROUNDING ELECTRODE CONDUCTOR IN MASONRY. 4) DRIVE RODS FLUSH OR BELOW GRADE. 5) TIGHTEN LB CONNECTION TO PANEL 6) CUT NAILS NOT ACCEPTABLE FOR ANCHORING SERVICE TO MASONRY ( PER AUTHORITY HAVING JURISDICTION) USE 1/4" HARDWARE OR BETTER. |