Permit: T05EL00485

Parcel: 135101260


Addresses:

2229 S CALLE ZAMORA

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/04/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) LABEL BREAKERS WITH PERMANENT MARKER. 2) INSTALL FILLER BLANK AT PANEL 3) ROMEX STAPLES NOT SUITABLE FOR SECURING GROUNDING ELECTRODE CONDUCTOR IN MASONRY. 4) DRIVE RODS FLUSH OR BELOW GRADE. 5) TIGHTEN LB CONNECTION TO PANEL 6) CUT NAILS NOT ACCEPTABLE FOR ANCHORING SERVICE TO MASONRY ( PER AUTHORITY HAVING JURISDICTION) USE 1/4" HARDWARE OR BETTER.