Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00464
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CLEARANCE SUBJECT TO BELOW LISTED REPAIR PLEASE READ CAREFULLY ANY QUESTIONS 954-0161 THERE ARE 13 ELECT SERVICES AT THIS COMPLEX ALL HAVE BEEN VANDALIZED IN THAT THE GROUNDING ELECTRODE CONDUCTOR HAS BEEN CUT STOLEN. A 1HR ELEC. REPAIR PERMIT WILL BE REQUIRED TO MAKE THE REPAIR AT EACH SERVICE. I ALSO SUGGEST YOU PROVIDE PHYSICAL PROTECTION OF THE GROUNDING ELECTRODE CONDUCTOR TO PREVENT ANY FUTURE THEFT. |
|
03/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE GROUNDING ELECTRODE CONDUCTOR HAS BEEN STOLEN ( CUT) FROM ELEC. SERVICE. THIS IS COMMON IN THAT ALL OF YOUR ELECT. SERVICES HAVE BEEN VANDALIZED IN THIS MANNER. IT IS UNSAFE IN THIS CONDITION. ALL SERVICES NEED TO BE REPAIRED PRIOR TO ENERGIZING AND CORRECTION IS CRITICAL THAT THE REPAIR IS MADE INMEDIATELY TO ASSURE SAFETY ON ALL ENERGIZED SERVICES. |