Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* PARTIAL OK TO CLEAR |
| 03/09/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) NEED MIN 2'' RIGID OR IMS RISER ( VERIFY PER UTILITY) 2) NEED 2 GROUND RODS MIN. 6' APART. 3) BOND GAS & WATER PIPES TO ELEC. SERVICE. 4) ATTACH SERVICE DIRECTLY TO MANSORY & ATTACH RISER TO UNISTRUT OR SOMETHING THAT WILL HOLD UP TO WEATHER. |