Permit: T05EL00450

Parcel: 136350070


Addresses:

8403 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEED BONDING BUSHING & SHORT NIPPLE AT 1/2LB TO BOND CONDUIT TO PANEL 2) APPLY ANTI OX PASTE AROUND ALL OF THE CODUCTOR @ MAIN & 50 AMP CIRCUIT BREAKER 3) EXPOSE GROUND RODS FOR INSPECTION 4) BOND GAS LINE @ SERVICE