Inspection History: ELECTRIC - FINAL

Permit Number - T05EL00433

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/29/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR WILL NOTIFY TEP ON CLEARANCE
03/24/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) THE ADDRESS ON THE SERVICE MUST BE THE SAME AS THE PERMIT OR I AM NOT ALLOWED TO CLEAR SERVICE. SERVICE 1625 E PRINCE OWNER # 14 PERMIT 1625 E PRINCE. CONTACT PERMIT COUNTER AT DSD 791-5550 TO CORRECT. BOTH PERMI AND SERVICE MUST HAVE SAME ADDRESS. #2 1/2" EMT PENETRATION TO SERVICE PANEL IS ABOVE THE BOTTOM OF THE BUS LINE. THE LOCKNUT ON 1/2" MUST BE A SEALING TYPE. #3 LABEL LAST BREAKER AS ROOF LIGHT ON ROOF ?PS