Permit: T05EL00412

Parcel: 122121550


Addresses:

4619 E CALLE CORTA

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/05/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/17/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :* FINISH CUTOVER & RESCHEDULE FINAL. OK TO CLEAR.
03/15/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :* 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 2) A 2ND GROUND ROD IS NEEDED. 3) GAS AND WATER BONDS ARE NEEDED. 4) A BOND BUSHING IS NEEDED FOR RISER. 5) TEP RISER TO HAVE 1/4" MINIMUM HARDWARE. 6) STRAP GROUND TO BUILDING