Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/16/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) CLEAN SURFACE UNDER GROUND LUG 250.12 2) PLEASE IDENTIFY GROUNDING CONDUCTOR 250.119 ( JUNCTION BOX) 3) COMPLETE # 3 OF PREVIOUS INSPECTION. |
| 03/02/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) ADDRESS LABEL TO BE SCREWED OR RIVETED. 2) IDENTIFY NEUTRAL CLOSER TO WHETHER HEAD. 3) PLEASE VERIFY PERMIT FOR NEW A/C INSTALLATION. 4) RECALL AFTER CROSS OVER. OK TO CLEAR RESIDENTIAL INC |