Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T05EL00396
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* CLEARANCE SUBJECT TO PLUMBING APPROVAL. ALL CORRECTIONS HAVE BEEN CORRECTED. STILL PLUMBING IS NEEDED AS WELL AS FINAL PLUMBING APPROVAL | |
03/04/2005 | ELECTRIC - RECONNECT | Cancelled | GLORYA OCCUPANT OF COMMERCIAL BLDG CALLED AND CANCELLED INSPECTION AT 8:17 AM ON 03/04/05 #990-2830 | |
03/04/2005 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* DENIED NOT READY | |
03/01/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HANDY BOXES TO SMALL FOR WIREFILL. HAND BOXES ALONG EAST WALL ARE IMPROPERLY WIRED WITH N.M. CABLE (INSTALL APPROVED WIRING METHOD SUCH AS E.M.T. OR M.C. CABLE AND USE THE PROPER CONNECTORS) (ALSO BELOW COUNTER AT REGISTER) 2) CLEAN UP WIRING IN CEILING (EXPOSED THHN CONDUCTORS) ALSO HORIZONTAL LIGHTING NEEDS SIESMIC SUPPORT 3) SEAL OPEN KNOCKOUTS IN BOXES AT STATION 4) INSTALL GROUNDING ELECTRODE SYSTEM AT SERVICE (HAS BEEN CUT-STOLEN FROM SERVICE EQUIPMENT) 5) RECEPTACLES NEAR SINK LOCATIONS TO BE GFCI PROTECTED 6) NEED PLUMBING INSPECTION APPROVAL OF NEW PLUMBING THAT HAS BEEN INSTALLED 7) ADDRESS TO MATCH PERMIT ADDRESS AND ELECTRIC METER |