Permit: T05EL00396

Parcel: 131050030


Addresses:

5466 E 29TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05EL00396

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
03/09/2005 ELECTRIC - RECONNECT Approved IVRS - Inspection :* CLEARANCE SUBJECT TO PLUMBING APPROVAL. ALL CORRECTIONS HAVE BEEN CORRECTED. STILL PLUMBING IS NEEDED AS WELL AS FINAL PLUMBING APPROVAL
03/04/2005 ELECTRIC - RECONNECT Cancelled GLORYA OCCUPANT OF COMMERCIAL BLDG CALLED AND CANCELLED INSPECTION AT 8:17 AM ON 03/04/05 #990-2830
03/04/2005 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :* DENIED NOT READY
03/01/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HANDY BOXES TO SMALL FOR WIREFILL. HAND BOXES ALONG EAST WALL ARE IMPROPERLY WIRED WITH N.M. CABLE (INSTALL APPROVED WIRING METHOD SUCH AS E.M.T. OR M.C. CABLE AND USE THE PROPER CONNECTORS) (ALSO BELOW COUNTER AT REGISTER)
2) CLEAN UP WIRING IN CEILING (EXPOSED THHN CONDUCTORS) ALSO HORIZONTAL LIGHTING NEEDS SIESMIC SUPPORT
3) SEAL OPEN KNOCKOUTS IN BOXES AT STATION
4) INSTALL GROUNDING ELECTRODE SYSTEM AT SERVICE (HAS BEEN CUT-STOLEN FROM SERVICE EQUIPMENT)
5) RECEPTACLES NEAR SINK LOCATIONS TO BE GFCI PROTECTED
6) NEED PLUMBING INSPECTION APPROVAL OF NEW PLUMBING THAT HAS BEEN INSTALLED
7) ADDRESS TO MATCH PERMIT ADDRESS AND ELECTRIC METER