Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 05/27/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* / WORK HAS BEEN DONE TO INTERIOR WOP AREAS ARE IN BACKROOM AND CENTER ALCOVE. PLEASE ADD TO NEW WORK TO BE DONE OR OBTAIN PERMIT FOR WORK TO BE PROPERLY INSTALLED AS PER CODES. WORK MAY BE REMOVED. | |
| 05/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE COMPLETE ITEMS #2 AND 6 OF PREVIOUS INSPECTION |
|
| 05/04/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BOXES WITH MORE THAN 1/4" FROM BOX TO SURFACE IN NON COMBUSTIBLE AND FLUSH AT COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20 2) FILL UNUSED OPENINGS IN BOXES 3) WE HAVE EXPOSED CONDUCTORS 4) PLEASE PROVIDE PHYSICAL PROTECTION FOR NM CABLES 5) LIGHT FIXTURES MOUNTED ON COMBUSTIBLES TO HAVE JUNCTION BOXES 6) PLEASE VERIFY PERMITS FOR NEW WORK ON INTERIOR |