Permit: T05EL00389

Parcel: 120061160


Addresses:

319 E LINCOLN ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
03/14/2005 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
03/10/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) INSTALL BOND SCREW OR BOND NEUTRAL BAR IN SERVICE DISCONNECT, INSTALL BREAKER BLANKS IN PANEL. 2) UNIT MUST BE OPEN FOR INSPECTION. RE-CALL FOR INSPECTION.
02/28/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) EXISTING DISCONNECT SWITCH AT SERVICE NEEDS TO BE REPLACED WITH RAINTITE, WATER DAMAGE INSIDE DUE TO USE OF INDOOR TYPE NOT RATED FOR OUTDOOR USE, OR UPGRADE SERVICE. 2) NEW J-BOXES OUTSIDE ALONG ROOT LINE NOT APPROVED FOR OUTDOOR USE. 3) SHADE RAMADA IN FRONT OF HOUSE FALLING DOWN, RE-BRACE POSTS OR TAKE DOWN. 4) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO ENCLOSURE. IF SERVICE IS UPGRADED BE SURE TO ADD TO THIS PERMIT DESCRIPTON. 5) ROMEX WIRING INSIDE ENTRY AREA INSTALLED IN WALLS NOT PER CODE. MUST BE INSIDE WALL AT LEAST 1 1/4" DEPTH.