Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit: T05EL00374

Parcel: 133047040

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/22/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR RESIDENTIAL UPGRADE
03/15/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) SEAL ENTRANCE WITH APPROVED FITTING ABOVE CURRENT CARRING PARTS. 2) GAS BOND TO BE CONNECTED TO INTERIOR SIDE PIPING
02/24/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* RE INSPECTION FEE DUE PRIOR TO NEXT INSPECTION. 1) INSTALL BONDING BUSHING AT 2 1/2" RISER. 2) SECURE GROUNDING ELECTRODE CONDUCTOR TO WALL. 3) USE ONLY BREAKERS APPROVED BY PANEL MANUFACTURER. 4) ALUM. CONDUCTOR TERMINATIONS REQUIRE ANTI OXIDATION PASTE. 5) INSTALL THE PROPER # OF CIRCUITS. 6) REMOVE ALUM. CONDUCTOR ( #6) OFF OF 100AMP BACK FED MAIN BREAKER. 7) KNOCKOUT BUSHING IS & CUT ( DAMAGED) PLEASE REPLACE WITH ONE THAT IS NOT CUT OR BROKEN. 8) 1/2" LB CONNECTION INTO PANEL IS LOOSE ( BOTH OF THEM) 9) 2 1/2" LOCKNUT IS LOOSE 10) SERVICE PANEL IS LOOSE PLEASE SECURE ADEQUATELY 11) NEUTRAL & EQUIP. GROUNDING CONDUCTORS ARE NOT TO BE MULTIPLE LUGGED ( TERMINATED UNDER SAME OPENING) UNLESS LABELED AS SUCH BY PANEL MANUFACTURER 12) PANEL APPEARS TOO SMALL FOR THE AMOUNT OF CONNECTED CIRCUITS 13) INSTALL THE BRASS W/HOLE IN IT TAMPER PROOF SCREW ON TEP SECTION OF SERVICE