Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR RESIDENTIAL UPGRADE | |
| 03/15/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SEAL ENTRANCE WITH APPROVED FITTING ABOVE CURRENT CARRING PARTS. 2) GAS BOND TO BE CONNECTED TO INTERIOR SIDE PIPING | |
| 02/24/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RE INSPECTION FEE DUE PRIOR TO NEXT INSPECTION. 1) INSTALL BONDING BUSHING AT 2 1/2" RISER. 2) SECURE GROUNDING ELECTRODE CONDUCTOR TO WALL. 3) USE ONLY BREAKERS APPROVED BY PANEL MANUFACTURER. 4) ALUM. CONDUCTOR TERMINATIONS REQUIRE ANTI OXIDATION PASTE. 5) INSTALL THE PROPER # OF CIRCUITS. 6) REMOVE ALUM. CONDUCTOR ( #6) OFF OF 100AMP BACK FED MAIN BREAKER. 7) KNOCKOUT BUSHING IS & CUT ( DAMAGED) PLEASE REPLACE WITH ONE THAT IS NOT CUT OR BROKEN. 8) 1/2" LB CONNECTION INTO PANEL IS LOOSE ( BOTH OF THEM) 9) 2 1/2" LOCKNUT IS LOOSE 10) SERVICE PANEL IS LOOSE PLEASE SECURE ADEQUATELY 11) NEUTRAL & EQUIP. GROUNDING CONDUCTORS ARE NOT TO BE MULTIPLE LUGGED ( TERMINATED UNDER SAME OPENING) UNLESS LABELED AS SUCH BY PANEL MANUFACTURER 12) PANEL APPEARS TOO SMALL FOR THE AMOUNT OF CONNECTED CIRCUITS 13) INSTALL THE BRASS W/HOLE IN IT TAMPER PROOF SCREW ON TEP SECTION OF SERVICE |