Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR | |
| 02/24/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FAN NEEDS 3 WIRE NOT 2 WIRE CORD OR REMOVE. 2) NEED PROPER N.M CONNECTOR AT HOOD. 3) OPEN LAMP FIXTURES NOT ALLOWED AT CLOSET. 4) DRYER RECEPTACLE MISSING COVER. 5) FUSED PULL OUT MISSING PULL OUT BLOCK AT A.C EQUIP. ( NEXT TO SERVICE) |