Permit: T05EL00326

Parcel: 131111180


Addresses:

5757 E 30TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/25/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR
02/16/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) 2 GROUND RODS REQUIRED NOW, AT LEAST 6' APART. 2) A GAS BOND IS ALSO REQUIED _ YOU CAN JUMPER A WIRE FROM WATER LINE TO GAS LINE OUTSIDE NEAR WHERE WATER BOND IS CONNECTED. 3) SERVICE HAD TO HAVE A METAL ADDRESS OR PAINT. NO MARKERS. 4) REMOVE DOUBLE LUGGING ON EXISTING BREAKERS. 5) STRAP 2" RISER UNDER ROOF.