Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK NEON TUBING ON BUILDING | |
| 03/17/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEW SPLICE BOOTS TO BE LISTED FOR WEATHERPROOF. 2) GTO TO BE SLEEVED WITH LISTED WEATHERPROOF SLEEVING. 3) SEAL TITE TO USE LISTED FITTING AND BOND TO METAL CHANNEL. 4) SUPPORT M/C CABLE 12" FROM BOXES AND FITTINGS AND AT 6' INTERVALS. 5) USE LISTED M/C CONNECTORS. | |
| 03/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PERMIT T05EL00316 BY YOUNG ELECTRIC SIGN OBTAINED , OK TO CLOSE OUT COMPLAINT. . NO ACCESS TO ROOF . NO YOUNG SIGN PEOPLE ON SITE. WILL NEED PLANS AND PERMIT. |