Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO CLEAR SER INC | |
| 03/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRES TO BE MADE UP IN A NEAT & WORKMANSHIP MANNER AT SER.PANEL. 2) INSTALL BONDING BUSHING AT A.C CONDUIT FEED TO BOND E.M.T ( CONCENTRIC ENCOUNTERED AT BOTH SER. PANEL & A.C DISCONNECT SWITCH. 3) I COULDN'T LOCATE OTHE 2ND GROUND ROD ( ONE NORTH OF A.C NEED TO DRIVE FLUSH OR BELOW GRADE). 4) WHERE IS THE WATER BOND CONNECTION TO SERVICE. 5) INSTALL 2" ROOF JACK FOR ROOF PENETRATION 6) SECURE GROUNDING ELECTRODE CONDUCTOR AT WALL ( BELOW PANEL) |