Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 02/23/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/14/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) ROOF TOP RECEPTS MUST BE IN W/P BOXES WITH W/P COVERS, GFCI PRTECTED. 2) WASHER OUTLET MUST BE IN WEATHER PROOF BOX & COVER, GFCI PROTECTED, DRYER OULET. ALSO IN W/P BOX & COVER, ALSO SWITCH BY OUTLETS. 3) INSTALL MISSING COVERS FOR AC UNIT/FURNACE. 4) FUSE PANEL BEHIND KITCHEN CABINET NOT ACCESSIBLE- CHECK FOR OVERSIZE FUSES. 5) NO ENTRY LIGHT OUSIDE FRONT DOOR. WORK MUST BE DONE BY C-11 LICENSED CONTR. REC-CALL INSP. WHEN DONE. |