Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR |
|
| 02/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 02/18/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* THE FOLLOWING MUST BE ADDRESSED BEYOND LIST LEFT BY INSPECTOR SUBA. 1) THE 150 A ZIN? CIRCUIT BREAKER AT HOUSE MAIN PANEL MUST BE REPLACED. 2) GROUNDING CIRCUITS MUST BE ESTABLISHED FOR BOTH ENDS. _ MAIN SERVICE LOCATION AND AT MAIN HOUSE SUB PANELS. 3) CHECK NEC FOR CLEARANCES FROM GOUND ON AERIAL CABLE ( SUB CIRCUIT-NOT SERVICE CONDUCTORS). 4) REMOVE EXTENSION CORD & PLUGIN OF EXTERIOR LIGHTS. |
|
| 02/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING RECEPTACLES NOT ALLOWED ON 2 WIRE CIRCUITS UNLESS FGCI PROTETED. 2) JUNCTION OPEN J-BOX OR INSTALL MISSING RECEPTACLE. 3) PROPERLY JUNCTION OPEN WIRE IN WATER HEATER CLOSET 4) REPLACE DAMAGED RECEPTACLES 5) EXPOSED ROMEX NOT ACCEPTABLE( OUTSIDE AT CARPORT DOOR) 6) INSTALL SMOKE DETECTORS IN BEDROOMS 7) NEED ACCESS TO REAR BUILDING |