Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00285
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/17/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*BONDING JUMPER TO BE SIZED PER 250.102 & 250.6 | |
03/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ATTACH GROUNDING ELECTRODE CONDUCTOR DIRECTLY TO NEUTRAL ( WITH OUT SPLICE) 2) BOND BONDING BUSHING AT LINE SIDE CABINET ENTRY |