Permit: T05EL00277

Parcel: 117050550


Addresses:

439 N 6TH AV #139

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/02/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* NOTE: WE CAN ONLY CLEAR ADDRESS AS IS LISTED ON THE PERMIT. THE LAST TIME I WAS HERE I NOTED ON ITEM 6) ADD SUITE # TO PERMIT ( DOESN'T LOOK LIKE THIS WAS DONE) ( THIS WILL BE CLEARED AS 439 N 6TH AV) ( W/OUT SUITE #)
02/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* TO BE INSPECTED BY TFD. 1) NEED PROPER WORKING CLEARANCE IN FRONT OF ELEC. PANEL. ( PLEASE RELOCATED TABLE SO WE CAN INSPECT ELEC PANEL) 2) CONDUIT THROUGHOUT NEEDS PROPER SUPPORT. 3) CAP OPNE SEWER WASTE LINES 4) OPEN J-BOX IN BATHROOM NEEDS COVER INSTALLED. 5) REMOVE DEBRIS IN FRONT OF SERVICE EQUIP. ( NEED MIN 36" WORKING CLEARANCE) 6) ADD SUITE # TO ADDRESS ON PERMIT