Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK TO CLEAR SERVICE INCREASE |
| 02/08/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*1) BLUE WIRE NUTS NOT LISTED FOR LARGER THAN # 8 CONDUCTOR 2) BOND JUNCTION BOXES. 3) SPLIT BOLTS NOT LISTED FOR MORE THAN A " RUN & A TRAP" 4) BONDING JUMPERS ON LI?? SIDE TO BE SIZED PER 250.102 & 250.66 5) CLEAN SURFACE UNDER LUG 6) PLEASE PROTECT CABLES ENTERING CONDUITS. 7) GROUNDED CONDUCTOR # 6 OR SMALLER TO BE WHITE ENTIRE LENGTH 200.6 (A) |