Permit: T05EL00256

Parcel: 11006097A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR SERVICE INCREASE
02/08/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*1) BLUE WIRE NUTS NOT LISTED FOR LARGER THAN # 8 CONDUCTOR 2) BOND JUNCTION BOXES. 3) SPLIT BOLTS NOT LISTED FOR MORE THAN A " RUN & A TRAP" 4) BONDING JUMPERS ON LI?? SIDE TO BE SIZED PER 250.102 & 250.66 5) CLEAN SURFACE UNDER LUG 6) PLEASE PROTECT CABLES ENTERING CONDUITS. 7) GROUNDED CONDUCTOR # 6 OR SMALLER TO BE WHITE ENTIRE LENGTH 200.6 (A)