Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* NOTES: SERVICE FOR ELECTRIAL OK HOWEVER NO CLEARANCE FOR POWER UNITL PERMITS FOR OTHER WORK OBTAINED- SEE NOTE PREVIOUS INSPECTION. WALLS OK FOR ROUGH ELECT. | |
| 03/02/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ( ADD MECHANICAL TO PERMIT W/PLANS, NEED PLUMBING TOO FOR NEW GAS PACK ON ROOF) 1) SMOKE DETECTOR TOO CLOSE AT N. EAST BEDROOM (2) N.M CABLE NOT PROPERLY SECURED AT S. EAST B.R SWITCH. 3) OPEN DRYWALL SO I CAN FOLLOW SMOKE DETECTOR WIRING 4) FHA STRAPS NEEDED 5) CUT DRYWALL HIGHER AT S.EAST BEDROOM@ SOUTH WALL SO I CAN INSPECT WIRING 6) METAL BOXES TO BE PROPERLY GROUNDED USING PROPER GROUNDING SCREWS 7) NEED MIN 6" OF WIRE FOR MAKE UP AT EACH DEVICE & J-BOX 8) OPEN CEILING SO I CAN INSPECT DINING WIRING & PORCH SWITCH WIRING. 9) REVISE PLANS TO SHOW CORRECT RISER SIZE THAT WAS INSTALLED & ALL IN ONE EQUIP. 10) NEED ADDITIONAL ( RECEPTACLE) AT LIVING ROOM( MORE THAN 6' FROM HALL DOORWAY. |