Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/09/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* NOTES: 1) BOND WATER LINE, NOT SEWER LINE. | |
| 02/07/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BONDING BUSHING ON 3/4" PANEL FEEDER. 2) INSTALL LOCKNUT BETWEEN PANEL & LB. 3) INSTALL WHITE NEUTRAL CONDUCTOR DO NOT TAPE # 12. 4) INSTALL BOND SCREW AT NEUTRAL BUS ( SERVICE EQUIP ) 5) BOND WATER & GAS 6) DRIVE RODS FLUSH OR BELOW GRADE |