Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05EL00251

Parcel: 120090970


Addresses:

4455 S 4TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/11/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/09/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :* NOTES: 1) BOND WATER LINE, NOT SEWER LINE.
02/07/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) INSTALL BONDING BUSHING ON 3/4" PANEL FEEDER. 2) INSTALL LOCKNUT BETWEEN PANEL & LB. 3) INSTALL WHITE NEUTRAL CONDUCTOR DO NOT TAPE # 12. 4) INSTALL BOND SCREW AT NEUTRAL BUS ( SERVICE EQUIP ) 5) BOND WATER & GAS 6) DRIVE RODS FLUSH OR BELOW GRADE