Permit: T05EL00226

Parcel: 106011060


Addresses:

610 E KNOX DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR INCREASE
03/02/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SERVICE DOES NOT MEET CLEARANCE REQUIREMENTS OF 2002 NEC 110-26 FOR BELOW & IN FRONT OF SERVICE. 2) 2ND GROUND ROD TO EAST CAN ONLY HAVE/ CONDUCTOR UNDER BARREL CLAMPS. 3) PANEL SCHEDULE NEEDS TO BE FILLED OUT. 4) SEAL HOLE IN OUTLET BOX COMPUTER ROOM