Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* OK TO CLEAR INC | |
| 02/07/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL INSULATED BUSHING ON PANEL SIDE OF 1 1/4 OFF SET NIPPLE & BONDING BUSHING @ METER SIDE OF OFFSET NIPPLE 2) INSTALL LOCKNUT BETWEEN LB & PANEL TO BOND LP & CONDUIT. 3) INSTALL WHITE NEUTRAL CONDUCTOR FOR BRANCH CIRCUITS AT PANEL. 4) BOND GAS & WATER TO SERVICE. 5) DRIVE RODS FLUSH O? BELOW GRADE. |