Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/25/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DENIED COVER ON EXISTING METER NOT INSTALLED YET. |
|
| 02/18/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* OK TO CLEA FOR C/D & T/S 200 AMP ( COMMERCIAL METER BASE-APPRD BY TEP? ) CALL FOR FINAL WHEN EQUIPMENT CUT-OVER IS COMPLETED. THANKS |
|
| 02/15/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* NOTE 1) THE GROUNDING ELECTRODE SYSTEM MUST CONSIST OF TWO 5/8" X 8' GROUND RODS. THESE MUST BE CONNECTED TOGETHER BY A #4 COPPER CONDUCTOR WHICH IS RUN TO THE NEUTRAL ?? OF THE MAIN SWITCH. THE RODS MUST BE SET NOT CLOSER THAN SIX ( 6') FEET (APART) THE COLD WATER AND GAS PIPING MUST BE BONDED TO THE METAL OF THE MAIN SWITCH. 2) THE ADDRESS LABEL ON THE METER MUST BE METAL ( ALUMINUM) EMBOSSED WITH THE NUMBERS. 3) THE TRENCH MUST BE APPROVED BY TEP. CORRECT & RECALL |
|
| 02/10/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NO GROUND ELECTRODE SYSTEM INSTALLED 2) NO ADDRESS LABEL ON SERVICE. 3) CHASE NIPPLES NOT ALLOWED USE CLOSE NIPPLES WITH LOCKNUTS, BONDING LOCKNUTS OR BOND BUSHINGS REQUIRED AHEAD OF OVER CURRENT PROTECTION. ALSO ON RISER CONDUIT. |