Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05EL00205

Parcel: 123030460


Addresses:

2813 E LEE ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CLEARANCE REQUIRED + 3' AWAY FROM WALL
03/04/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* REE FEE DUE- 2 ITEMS CALLED OUT LAST INPS WERE NOT CORRECTED. SEE #3 -COPPER GROUND GOING UP WALL FROM GAS BON? NOT SUPPORTED, SUPPORT ON ROOF ALSO. SEE #5 -NEC REQUIRED 3' OUT IN FRONT OF SERVICE
02/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* BOND?? CONNECTED 1) #2 NOT CORRECTED 2) SQ D CIRCUIT BREAKER CANNOT BE USED IN A CUTLER HAMMER PANEL. 3) SUPPORT #4 COPPER ON WALLS AT GAS AND WATER BOND AND ON ROOF, ALSO BE LOW SERVICE. 4) CORRECT SEALING LOCKNUT INSIDE PANEL TO KEEP WATER OUT. 5) BUSH IN FRONT OF SERVICE TO BER REMOVED OR RELOCATED-HAD TO LEAN OVER IT TO INSPECT PANEL CODE CALLS FOR 3' OUT AND DOWN TO GRADE AND 15" WIDE CLEARANCE.
02/03/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210* PLEASE CORRECT, 1) CIRCUIT DIRECTORY. 2) ALL CIRCUIT BREAKERS FOR RECEP & LITING ARE 20AMP. IN A HOUSE BUILT DURING THE 1950'S LITING & LIGHT USE CIRCUITS WERE RUN IN # 14 WIRE WHICH REQUIRED FUSE OR CIRCUIT BREAKER NOT LARGE THAN 15 AMP. UNLESS YOU HAVE REWIRED THE INTERIOR THIS STILL APPLIES. RESEARCH YOUR CIRCUITS AND ? THEM ACCORDING TO WIRE SIZE.3) WHEN ARE THE GAS PIPE AND COLD WATER PIPE GROUND BONDS? LEAVE NOTE WITH INFO AND MAP.