Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2005 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 02/15/2005 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode conn BE ADVISED, 1) NEW SERVICES REQUIRE NEW GROUNDING SYSTEM. 2) THE NEW GRDQ SYSTEM MUST CONSIST OF TWO 5/8 X 8' GROND RODS DRIVEN TO 2" BELOW NATURAL GRADE. YOU MAY DRIVE THESE INSIDE THE NEW TRENCH. LOCATE THEM 'AT LEAST 6 FT. APART. THE GAS PIPING AND COLD WATER PIPING MUST ALSO BE GROUNDED TO THE PANEL. CLAP ON TO THE HOUSE SIDE OF THE PIPING. 3) PLEASE CALL TEP AND REQUEST A TRENCH INSPECTION. THEY SET THE RULES FOR DEPTH, WIDTH, ETC. COMPLETE & RECALL. THANKS. P.S INSTALL METAL STRIP ADDRESSS ABOVE OR BELOW METER. |