Permit: T05EL00197

Parcel: 123041140


Addresses:

2821 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
02/16/2005 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
02/15/2005 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn BE ADVISED, 1) NEW SERVICES REQUIRE NEW GROUNDING SYSTEM. 2) THE NEW GRDQ SYSTEM MUST CONSIST OF TWO 5/8 X 8' GROND RODS DRIVEN TO 2" BELOW NATURAL GRADE. YOU MAY DRIVE THESE INSIDE THE NEW TRENCH. LOCATE THEM 'AT LEAST 6 FT. APART. THE GAS PIPING AND COLD WATER PIPING MUST ALSO BE GROUNDED TO THE PANEL. CLAP ON TO THE HOUSE SIDE OF THE PIPING. 3) PLEASE CALL TEP AND REQUEST A TRENCH INSPECTION. THEY SET THE RULES FOR DEPTH, WIDTH, ETC. COMPLETE & RECALL. THANKS. P.S INSTALL METAL STRIP ADDRESSS ABOVE OR BELOW METER.