Permit: T05EL00188

Parcel: 11006097B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE. 2) BLUE WIRE NUTS NOT LISTED FOR LARGER THAN # 8 CONDUCTOR 3) BOND JUNCTION BOXES 4) SPLIT BOLTS NOT LISTED FOR MORE THAN "A? & TAP" 5) BONDING JUMPE? ON LINE SIDE TO BE ?? PER 250.102 & 205.66 6) PLEASE PROTECT CABLES ENTERING CONDUITS 7) CLEAN SURFACE UNDER LUG 8) GROUNDED CONDUCTOR # 6 OR SMALLER TO BE WHITE ENTIRE LENGHT 200.6 ( A)