Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL CORRECT SIZED TYPE 5 FUSES AT BRANCH CIRCUITS ( SUB PANEL ) 2) GROUNDING TYPE RECEPTACLES ARE NOT ALLOWED UNLESS CONNECTED TO AN EQUIP. GROUNDING CONDUCTOR OR GFCI PROTECTED. 3) OUTDOOR RECEPTACLE NEEDS TO BE GFCI PROTECTED. 4) POWER LINES ARE TOO LOW ( PROVIDE NEW POINT OF ATTACHMENT FOR T.E.P MIN. 12' ABOVE FINISHED GRADE. |