Permit: T05EL00184

Parcel: 115020620


Addresses:

530 E LINDEN ST #01

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/31/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) INSTALL CORRECT SIZED TYPE 5 FUSES AT BRANCH CIRCUITS ( SUB PANEL ) 2) GROUNDING TYPE RECEPTACLES ARE NOT ALLOWED UNLESS CONNECTED TO AN EQUIP. GROUNDING CONDUCTOR OR GFCI PROTECTED. 3) OUTDOOR RECEPTACLE NEEDS TO BE GFCI PROTECTED. 4) POWER LINES ARE TOO LOW ( PROVIDE NEW POINT OF ATTACHMENT FOR T.E.P MIN. 12' ABOVE FINISHED GRADE.