Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T05EL00167
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :*APPROVED OK TO CLEAR RECONNECT. | |
01/26/2005 | ELECTRIC - RECONNECT | Denied | CALLE D9:50 AM LEFT MESSAGE 1) GROND WIRE TO SERVICE HAS BEEN CUT OFF NEETO TO INSTALL ONE GROUND ROD PLUS WATER BOND 2) REMOVE UNLISTED BREAKERS FROM PANEL, SEE LABEL INSIDE PANEL FOR APPROVED ONES. 3) QUARTZ LIGHTING ON OUTSIDE POLES TO BE FIXED AND ARE REQUIRED TO POINT DOWN ONLY AS PER CITY OF TUCSON LIGHTING ORDINANCE. 4) ELECTRICAL WIRING OUTSIDE ON NORTH WALL, ALL WIRING TO BE WEATHERPROOF, AND PROPERLY SUPPORTED. PLEASE NOTIFY OWNER WORK IS TO BE DONE BY A LIC ELECTRICAL CONTRACTOR. |