Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/31/2005 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* OK ROUGH ELECTRIC |
| 01/26/2005 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* NOT READY 1) PROTECT CONDUCTORS IN BOXES AS PER 314.43. 2) CONDUIT TO BE 18" IN DEPTH AS PER 300.5 3) USE BOX TO BE LISTED FOR CEILING FAN 4) SUPPORT ?? CABLE WITHIN 12" OF CAN JUNCTION BOXES. 5) BOXES TO BE FLUSH IN COMUSTIBLES 314. 20. 6) GROUND METAL BOXES 7) MAKE UP WIRING 8) CONDUCTORS TO EXIT BOX 6" FROM POINT OF ENTRY 300.14 |