Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* OK TO CLEAR | |
| 02/03/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUNDING ELECTRODE CONDUCTOR UNSPLICED TO NEUTRAL BUS. 2) #6 CONDUCTOR TOO SMALL WITHOUT PHYSICAL PROTECTION ( INSTALL #4 WATER & GAS BOND. 3) G.E.C TERMINATED INCORRECTLY AT EAST GROUNDING ELECTRODE. 4) REMOVE WOOD BEHIND PANEL & MOUNT DRECTLY TO MASONRY. 5) RISER HAS NOT SUPPORT ?? N.E.C & TEP REQUIREMENTS. 6) METER BASE NOT TO EXCEED 6' 3" TO CENTER PER TEP ( AT SOCKET) 7) BOND WATER INTERIOR SIDE OR ??UNION. 8) NEED LIC. CONTRACTOR CALL ME 954-0161 9) LOCKNUT IS BACKWARDS AT LB 10) SECURE EMT PER NEC. 11) BRANCH CIRCUIT GROUNDING CONDUCTOR IMPROPERLY SPLICED |