Permit: T05EL00139

Parcel: 135080690


Addresses:

7218 E SYLVANE DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/22/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :* OK TO CLEAR
02/03/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) INSTALL GROUNDING ELECTRODE CONDUCTOR UNSPLICED TO NEUTRAL BUS. 2) #6 CONDUCTOR TOO SMALL WITHOUT PHYSICAL PROTECTION ( INSTALL #4 WATER & GAS BOND. 3) G.E.C TERMINATED INCORRECTLY AT EAST GROUNDING ELECTRODE. 4) REMOVE WOOD BEHIND PANEL & MOUNT DRECTLY TO MASONRY. 5) RISER HAS NOT SUPPORT ?? N.E.C & TEP REQUIREMENTS. 6) METER BASE NOT TO EXCEED 6' 3" TO CENTER PER TEP ( AT SOCKET) 7) BOND WATER INTERIOR SIDE OR ??UNION. 8) NEED LIC. CONTRACTOR CALL ME 954-0161 9) LOCKNUT IS BACKWARDS AT LB 10) SECURE EMT PER NEC. 11) BRANCH CIRCUIT GROUNDING CONDUCTOR IMPROPERLY SPLICED