Permit: T05EL00128

Parcel: 122173640


Addresses:

3128 E ADAMS ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/25/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :* OK TO CLEAR INC
01/21/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) WHERE IS THE WATER AND GAS BOND. 2) GROND RODS TO BE DRIVEN TO GRADE OR BELOW PER CODE 3) REMOVE 1/2" STRAP INSIDE SERVICE AT TOP RH SIDE ( NOT SUPOSSED TO BE IN THERE) 4) THE SERVICE PANEL REQUIRES 36" IN FRONT OF AND DOWN TO GROUND CLEARANCE, THE BUSH IN FRONT OF SERVICE DOES NOT ALLOW SOMEONE TO STAND IN FRONT OF PANEL WITH PROPER CLEARANCES. 5) VERIFY PVC ABOVE SERVICE IS SCHEDULE 80