Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* OK TO CLEAR INC | |
| 01/21/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHERE IS THE WATER AND GAS BOND. 2) GROND RODS TO BE DRIVEN TO GRADE OR BELOW PER CODE 3) REMOVE 1/2" STRAP INSIDE SERVICE AT TOP RH SIDE ( NOT SUPOSSED TO BE IN THERE) 4) THE SERVICE PANEL REQUIRES 36" IN FRONT OF AND DOWN TO GROUND CLEARANCE, THE BUSH IN FRONT OF SERVICE DOES NOT ALLOW SOMEONE TO STAND IN FRONT OF PANEL WITH PROPER CLEARANCES. 5) VERIFY PVC ABOVE SERVICE IS SCHEDULE 80 |