Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR RECONNECT |
|
| 07/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY BOND NEUTRAL CONDUCTOR AT SERVICE |
|
| 07/19/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEUTRAL STILL NOT CORRECTLY BONDED AT SERVICE 2) 6/3 ROMEX WAS ADDED FOR SUB-PANEL IN BLDG NOT ROUTED CORRECTLY IN DISCONNECT AT SERVICE, BOND NEUTRAL AND SEPERATE GROUNDS AND NETURALS IN PANEL OUTSIDE 3) LOAD WIRING NOT TO BE INSTALLED WITH ? TIE WIRING IN MAIN SERVICE DISCONNECT, RE-ROUTE LOAD CIRCUITS FROM PANEL 4) NEW FEEDER INSTALLED IN SUB-PANEL MUST HAVE PROPER CLAMP TYPE CONNECTED. ALSO SEPERATE GROUNDS AND NEUTRALS 5) STRANDED WIRE CANNOT BE WRAPPED AROUND SCREWS AT TERMINATIONS, USE LISTED LUGS |
|
| 07/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NOTES: SEE NOTES (2) INSPECTION, WIRING AT SERVICE STILL NOT TO CODE, DBL LUGGING IN MAIN SERVICE DISCONNECT NOT ALLOWED 2) NEUTRAL NOT BONDED PROPERLY AT SERVICE 3) NO FURTHER INSPECTIONS UNTIL REPAIR PERMIT ISSUED AND CALLED IN FOR INSPECTION 4) RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION-IF NO COMPLIANCE |
|
| 03/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) COVER PLATES MISSING ON EAST OFFICE FOR RECPT & LIGHT SWITCHES. 2) SEE NOTE # 3 OUTSIDE WIRING/ SPLICES FOR LIGHTS IN PARKING AREA NOT WIRED PER CODE SPLICES NEED TO BE IN APPROVED J-BOXES, LIGHT FIXTURES CANNOT EMIT LIGHT OUTWARDS, MUST HAVE SHIELDS TO EMIT LIGHT DOWN ONLY. 3) OBTAIN PERMIT FOR ELECTRICAL REPAIRS AS PER LAST INSPECTION. MUST USE L-11 LICENSED CONT. PLEASE READ NOTES. |
|
| 01/24/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE MUST BE SCREWED OR RIVITED TO COVER, NO MARKING PEN. 2) ELECTRIC SERVICE NOT GROUNDED PROPERLY-NEE 2 GROUND RODS 6' MIN APART. 3) OVERHEAD WIRES ON NORTH SIDE FRAYED BY WEATHER, NEED TO BE REPLACED WITH APPROVED CONDUCTORS FOR OUTSIDE USE. 40 THRERE ARE NUMEROUS EXPOSED SPLICES, WIRING METHODS OUTSIDE GARAGE AREA NOT PER CODE, NON WEATHER PROOF BOXES ETC. 5) NEED ACCESS TO UNIT EAST-LOCKED. 1-11 LICENSED CONTR. TO MAKE REPAIRS NECESSARY TO BRING HAZARDOUS WIRING UP TO CODE THRU-OUT PREMESIS PRIOR TO RELEASE OF POWER. OBTAIN 1 HR REPAIR PERMIT. LICENSED CONTR TO CONTACT RAY M OR DAN SANTA CRUZ 791-5550 EXT 1136 |