Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05EL00100

Parcel: 11623155E


Addresses:

601 W SIMPSON ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL00100

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/02/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PERMANENTLY MARK PANEL (MAIN)
2) PERMANENTLY MARK PANEL (ER)
3) IN PANEL ER 4-3/0 CU ENTRY NEEDS BUSHING ANY WHERE # 4 WIRE IS USED
4) #4 COPPER TO 2 GROUND RODS REQUIRED AT E-1
07/29/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY RUDY
07/27/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* DENIED
01/28/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* NOT READY