Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/16/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* APPROVED OK TO CLEAR |
| 03/03/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) ADDRESS LABEL TO BE SCREWED OR RIVITED TO PANEL. 2) PLEASE ADD NEW WASHER AND DRYER CIRCUITS TO PERMIT. 3) BOND JUNCTION BOX/GUTTER 250.148. 4) BLUE WIRE NUTS NOT LISTED FOR LARGER THAN # 8 CONDUCTORS. 5) GUY BACK BRACE SUPPORTS DESIGNED FOR RIGID/IMC CONDUITS NOT EMT SE SCREW CONNECTORS. 6) PERMIT ADDRESS IS INCORRECT PLEASE CHANGE. |