Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK TO CLEAR INC | |
| 01/24/2005 | ELECTRIC - FINAL | Cancelled | IVRS - Ri canceled | |
| 01/18/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WILL NOT ACCEPT ROMEX CONNECTOR FOR A TEMPORARY CONNECTION NEUTRAL TO NEUTRAL AT SERVICE LEAD. NEEDS TO BE CHANGED OUT BEFORE POSSING. 2) 3-GROUND WIRES UNDER GROUND BUSHING INSIDE PANEL NOT APPROVED -ONLY ONE CONDUCTOR. 3) SEAL OPENING AT SOUTH SIDE OF PANEL WHERE OLD CONDUCTORS ENTER BEHIND PANEL. 4) GATE LOCKED NO ANSWER AT DOOR -CANNOT SEE 2ND GROUND ROD, OR WATER OR GAS BOND. 5) CIRCUIT BREAKERS LISTED FOR USE INSIDE PANEL LABEL DO NOT QP ARE OK TO USE, USE LISTED TYPE. |