Permit: T05EL00061

Parcel: 113093390


Addresses:

1019 E COPPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*OK TO CLEAR INC
01/24/2005 ELECTRIC - FINAL Cancelled IVRS - Ri canceled
01/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) WILL NOT ACCEPT ROMEX CONNECTOR FOR A TEMPORARY CONNECTION NEUTRAL TO NEUTRAL AT SERVICE LEAD. NEEDS TO BE CHANGED OUT BEFORE POSSING. 2) 3-GROUND WIRES UNDER GROUND BUSHING INSIDE PANEL NOT APPROVED -ONLY ONE CONDUCTOR. 3) SEAL OPENING AT SOUTH SIDE OF PANEL WHERE OLD CONDUCTORS ENTER BEHIND PANEL. 4) GATE LOCKED NO ANSWER AT DOOR -CANNOT SEE 2ND GROUND ROD, OR WATER OR GAS BOND. 5) CIRCUIT BREAKERS LISTED FOR USE INSIDE PANEL LABEL DO NOT QP ARE OK TO USE, USE LISTED TYPE.