Permit: T05EL00050

Parcel: 122040400


Addresses:

4525 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/04/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/01/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) NEWLY INSTALLED PANEL ON INTERIOR OF CLOSET CANNOT BE USED AS A JUNCTION BOX. 2) IF INSULATION IS USED ROCK ?? WILL BE NEEDED NOT GLASS INSULATION. PLEASE LEAVE ACCESS ROOM TO JUNCTION BOX FOR INSPECTION.
03/31/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio 1) FILL UNUSED OPENING IN PASS THRU NIPPLE WITH NON-COMBUSTIBLE PRODUCT. 2) LABEL BREAKERS 3) NEED TO SEE INTERIOR JUNCTION BOX. 4) TIGHTEN LOOSE FITTINGS
03/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio. 1) USE APPROVED FITTING AT JUNCTION BOX. 2) NEW SUBPANEL NOT ALLOWED IN CLOSET 3) GAS B?UD TO BE TO INTERIOR SIDE OF PIPING. A REFEE HAS BEEN A??SSED PER ADMIN CODES. THIS THE 4TH INSPECTION.
02/11/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CONDITION #4 NOT MET
01/21/2005 ELECTRIC - FINAL Denied IVRS - Inspection :1) ATTACH METER TO TREATED LUMBER OR ATTCH TO MASONRY. 2) INSTALL BONDING BUSHING ON BOTH ENDS OF OFFSET NIPPLE 3) INSTALL METAL ADDRESS LABEL ON METER BASE PER T.E.P. 4) SERVICE SHOULD BE UPGRADED. DUE TO AGE & DILAPIDATED CONDITION OR EQUIPMENT