Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/01/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEWLY INSTALLED PANEL ON INTERIOR OF CLOSET CANNOT BE USED AS A JUNCTION BOX. 2) IF INSULATION IS USED ROCK ?? WILL BE NEEDED NOT GLASS INSULATION. PLEASE LEAVE ACCESS ROOM TO JUNCTION BOX FOR INSPECTION. | |
| 03/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1) FILL UNUSED OPENING IN PASS THRU NIPPLE WITH NON-COMBUSTIBLE PRODUCT. 2) LABEL BREAKERS 3) NEED TO SEE INTERIOR JUNCTION BOX. 4) TIGHTEN LOOSE FITTINGS |
|
| 03/28/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio. 1) USE APPROVED FITTING AT JUNCTION BOX. 2) NEW SUBPANEL NOT ALLOWED IN CLOSET 3) GAS B?UD TO BE TO INTERIOR SIDE OF PIPING. A REFEE HAS BEEN A??SSED PER ADMIN CODES. THIS THE 4TH INSPECTION. |
|
| 02/11/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONDITION #4 NOT MET |
|
| 01/21/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection :1) ATTACH METER TO TREATED LUMBER OR ATTCH TO MASONRY. 2) INSTALL BONDING BUSHING ON BOTH ENDS OF OFFSET NIPPLE 3) INSTALL METAL ADDRESS LABEL ON METER BASE PER T.E.P. 4) SERVICE SHOULD BE UPGRADED. DUE TO AGE & DILAPIDATED CONDITION OR EQUIPMENT |