Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/19/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE SEE PREVIOUS INSPECTION COMMENTS DENIED |
|
| 01/12/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)I.D. CIRCUIT BREAKERS 2)INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO ENCLOSURE. 3)SPA SHOULD BE ON GFI BREAKER, UNLESS ENTERNALY PROTECTED. VERIFY PERMIT ISSUED FOR SPA & APPROVED INSPECTIONS 4)INSTALL BUSHING TO PROTECT CABLES PASSING THRU - BACK OF ENCLOSURE 5)INSTALL BIND BUSHING ON BOTH ENDS OF 1 1/2" NIPPLE BETWEEN PANEL & METER BASE. |