Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/25/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The bonding is not per code.| 235* 1) GROUNDING INCORRECT |
|
| 05/04/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210*1. ONLY ONE GROUND SYSTEM IS REQUIRED FOR ALL FOUR METER PANELS. SEPARATE NEUTRAL & GROUND AT SUBPANELS. LEAVE ENDS OF RODS EXPOSED FOR INSPECTION. GROUNDING IS INCORRECT. SEE TYPICAL DIAGRAM BELOW |
|
| 04/27/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEPARATED GOUNDS & NEUTRALS 3319, 3321 SUB PANELS | |
| 02/25/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* LICENSED CONTRACTOR TO DO WORK. LICENSED CONTRACTOR TO BE ON SITE FOR INSPECTION |