Permit: T05EL00034

Parcel: 11007341A


Addresses:

4245 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05EL00034

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2005 ELECTRIC - RECONNECT Approved IVRS - Inspection :NOTE NEED T.I PERMIT. OK TO CLEAR
01/13/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSED THHN #12 CONDUCTOR WIRES AT CABINET ARE NOT INSTALLED PER NATIONAL ELECTRIC CODE (PLEASE REMOVE OR INSTALL CORRECTLY)
2) PROPERLY JUNCTION OPEN BOXES AND SEAL UNUSED CONDUIT OPENINGS THROUGHOUT
3) SEAL-INSTALL J-BOX COVER AT BOX BEHIND CABINET ( BELLOW (1) )
4) NEED ROOF ACCESS
5) FIXTURE END FALLING OFF FLOOR. FIXTURE UNDER NORTH OVERHANG
6) BELL TRANSFORMER CONNECTION SHOULD BE EXPOSED SPLICE