Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR PER MAC ON 1/13/05 |
|
| 01/06/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*/PLEASE CORRECT THE FOLLOWING: 1)THE GROUND WIRE IS LOCATED ON THE WRONG SIDE OF THE GROUND ROD CLAMP AT THE FIRST GROUND ROD. IT SHOULD BE IN THE "POCKET" SIDE 2)THE PHASING TAPE, WHT. & BLK & RD, SHOULD BE APPLIED NEAR THE WEATHERHEAD. 3)LEAVE A PIECE OF THE RISER SERVICE CABLE WITH THE PRINTED INTO ON THE GROUND BELOW THE PANEL SO I MAY CHECK SIZE, INSULATION AND IF IT IS "SUNLIGHT RESISTANT" 4)YOU HAVE #14 AWG WIRE TERMINATED ON 20 AMP BREAKERS. CHANGE THE BREAKERS TO 15 AMP. FILL OUT THE CIRCUIT DIRECTORY |