Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/14/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SQUARE CIRCUIT BREAKER CANNOT BE USED IN A 6E PANEL SEE PANEL LABEL. 2) TIGHTEN FLEX FITTING AT BOTTOM OF JUNCTION BOX. 3) COLER CODE-CITY ORD # 9287-120/208 BLACK/RED/BLUE. 4) SCREW HOLDING GROUND TO CAN AT JUNCTION BOX CANNOT BE USED 2002 NEC 250-8 USE NUT & BOLT. 5) SINCE THE LARGEST GROUND WIRE FROM PANEL TO J-BOX NEEDS TO BE #10 -2002 NEC 250-122. ON #3 ABOVE-IN OTHER THAN A RESIDENCE-FOR 3 PHASE WIRING YOU MUST USE BLACK-RED-BLUE YOU CANNOT USE ORANGE WHICH IS A 277/480 VOLT COLOR-CORRECT TAPING. REQUIRED AT PANEL JUNCTION BOX AND INSIDE PANEL WHERE ORANGE USED |