Case: T05DV00153

Parcel: 129132880


Addresses:

707 E 35TH ST

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
12/07/2005 INSP - FOLLOW UP CODE ENFORCE Approved HAZARDOUS WIRING REMOVED BY TENANT/OWNER
-KNOCKOUT BROKEN CUT, CAN CAUSE WIRING TO FRAY
LIGHT FIXTURES NOT PROPERLY INSTALLED, HANGING
-NOT SEALED
-NO VENT IN KITCHEN AND BATHROOM (JUST A HOLE)
-NO SMOKE DETECTORS
-HEATER NOT PRESENT IN KITCHEN BEDROOM.
-WALL MOUNTED HEATER IN LIVING ROOM (BASEBOUND)
-BEDROOM EGRESS BLOCKED
-DOOR ENTRY LACKING WEATHER STRIPPING, NOT PROPERLY SEALED.
-ELECTRICAL HAZARDS HAVE BEEN REMOVED, ALLOWING FOR NEW TENANTS TO OCCUPY UNIT AFTER POWER IS RESTORED.
11/23/2005 INSP - FOLLOW UP CODE ENFORCE Approved AMR3-23942 UNIT #1
AMR3-23944 UNIT #2 POWER CUT
AMR3-23945 UNIT #3

GAS METERS HAVE BEEN HIT BY A CAR ALL APPLIANCES HAVE BEEN CONVERTED TO ELECTRICITY. HOTWATER HEATERS 2 IN REAR WITHOUT PERMITS, GAS LIINE STILL PRESENT.
#W WATER HOSE EXTENDING FROM KITCHEN TO MACHINE MACHINE OUTSIDE NO WATER CONNECTION.

TENANT IN UNIT #2 REAR UNIT HAS NO POWER, TEP HAS CUT POWER FOR NON-PAYMENT.
TENANT IS BYPASSING METER AND RUNNING WIRES DIRECTLY INTO TEP SIDE OF METER. STEALING POWER.

OWNER STATES BARE WIRING INSIDE OF UNIT MANY SHOCK HAZARDS IN INTERIOR. NO WAY TO VERIFY IF HAZARDS IN INTERIOR. NO WAY TO VERIFY IF HAZARDS EXIST. DOOR HAS NEW LOCK, NOT PLANNED BY OWNER, NO KEY.

TEP INSPECTORS/INVESTIGATORS ON SITE TO VERIFY TYPE OF CONNECTION TENANT HAS USED TO SUPPLY POWER.

SERVICE CREW FROM TEP CALLED OUT TO DISCONNECT ILLEGAL TAP.

TAP DISCONNECTED, TEP PULLED WIRES FROM INTERIOR TO EXTERIOR AND CUT.
-LOCK PLACED ON METER
-DNR ISSUED NOV FOR HAZARDOUS ELECTRICITY CONNECTIONS AND SHUT DOWN UNIT.
-OWNER SIGNED NOV TENANTS CANNOT BE LOCATED.
-TEP PUT HOLD ON POWER UNTIL MINIMUM HOUSING INSPECTION IS CONDUCTED TO ABATE ELECTRICAL HAZARDS IN INTERIOR.