Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/13/2005 INSP - INITIAL CODE ENFORCMENT Approved T.P.D. CASE #0501130357, SGT. THOMPSON.
6 UNITS IN RESIDENCE.
BASEMENT IN HOUSE. MAIN, EXTENSION CORDS OUT OF WINDOWS. MACHINE SHOP, CARS, STRUCTURAL.
UNIT #2 BASEMENT UNIT:
CEILINGS LOW, BATHROOM NEEDS GFCI, WINDOW HEIGHT @ 4'' - 8'' AND 18'' H. X 3 1/2'' W.
MIN. RECEPT. SPARING ONLY ON SOME WALLS. CENTER BED. NO WALL SWITCH. UNIT MAY BE CONTAMINATED W/ MERSCA (A BACTERIA FOUND ON 'METH' USERS AND NOT CUREABLE.
- STAIRWELL USED AS STORAGE AND STANDARD GYPSUM WALL BOARD IS LINING THE DIAGONAL.
- 3 WAY SWITCH INOP. FOR STAIRWELL.
UPPER UNIT, N.N.E. ENTRY.
- ENTRY DOOR HAS DOUBLE CYLINDER LOCK.
- BEDROOM WINDOWS TOO HIGH.
UNIT #4 (N. STRUCTURE DUPLEX):
EXTERIOR STORAGE ROOM:
OPEN SPLICES, BROKEN RECEPTACLE AND COVERS. EXTENSION CORD USED AS PERMANENT WIRING METHOD.
PLUMBING LINES FROM WATER HEATER EXT. ENDING UNSUPPORTED.
SINGLE WIRING AT PANEL BOARD GOING THROUGH WALL.
DOUBLE LUGGING AT MAIN BREAKER.
DOUBLE LUGGING AT LUG FOR GROUND WIRES.
SINGLE CONDUCTOR PROTRUDE FROM STRUCTURE.
- NO ADDRESS TAG.
- NO ID FOR CIRCUITS.
- ROMEX GOING UNDERGROUND TO ? AND UNPROTECTED
- MAIN BOARD JUMPER MISSING.
- A/C DISCONNECTS UPSIDE DOWN (NON RAINTIGHT).
- LINE & LOAD CONNECTION ARE REVERESED AT A/C DISC.
- DOUBLE (#3) LUGG AT PANEL, I.D. CIRCUIT.
- EXCESSIVE USE OF EXTENTION CORD @ PORCH.
- KITCHEN SMALL
3'' - 10'' X 7'' - 8'' INTERIOR MEASUREMENTS.
- S.D. INOP.
- LACK OF EGRESS. (WINDOW HEIGHT)
- A/C WINDOW RECEPT. OVER FUSED AT 30 AMPS.
UNIT #7:
ROOM 9 1/2 X 11
LACKS S.D.
NOTE: 'D' GAS IS SHUT OFF.
GARAGE:
ROOF STRUCTURE 2X6 RAFTER 'OVER SPANNED' 30'' O.C.
/10'' TO CENTER SUPPORT AND ANOTHER AT 5FT.
WITH IN OVER SPANNED.
GARAGE WIRE W/ EXTENSION CORD, OPEN SPLICE, IMPROPER WIRING.
JANUARY 1ST NEW OWNER.