Case: T05DV00031

Parcel: 120071210


Addresses:

19 W LINCOLN ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/09/2006 INSP - INITIAL CODE ENFORCMENT Approved (1) 16-11 ELEC. SYS. TC 16-4 PERMITS REQUIRES UNITS A,B&C.
VIOLATION ABATED-NEW 100 AMP SEVICE HAS BEEN ISTALLED A TALL THREE UNITS
UNIT B NEW SERVICE LONG WITH NEW CIRCUITS INSTALLED THROUGH OUT STRUCTURE, NEW FCI RECEPTACLES ALSO INSTALLED INSPECTION TEST ON RECEPTACLES FOUND ILLEGAL FALSE GROUNDS IN ALL THREE UNITS OWNER WAS INSTRUCTURED TO ME CORRECTION MADE BY CONTRACTOR. UNITS A&C, NEW GFIC RECEPTACLES HAVE BEEN INSTALLED.
(2) TC 16-11 BUILDING ANTERIOR (A) FIRE SAFETY 1,2&3 TC 16-4 OERNUTS REQUIRED UNITS A,B,C.
(1) VIOLATION ABATED-NEW SMOKE DECTECTORS INSTALLED.
(2) VIOLATION ABATED-NEW WINDOWS ISTALLED THOUGH OUT STRUCTURES
(3) VIOLATION ABATED-SMALLER WINDOW REPLACED WITH CORRECT SIZE OPENING.
(3) TC 16-11 (B) HEATING I TC16-4 PERMITS TEQUITED UNITS A&C
(1) VIOLATION ABATED-OBSOLETE NON-FUNCTIONING FOURNANCE AND GAS LINE CAPPED OFF
(2) VIOLATION ABATED-NEW VALUE ISTALLED UNIT HAS BEEN SEVICED
(4) TC16-11 (E) PLUMBING SYSTEMS TC 16-4 PERIMITS REQUIRED UNITS A,B&C
(1) UNITS A&V-VIOLATION ABATED GAS LINES SCARED NEW ENCLOUSURE INSTALLED NDER COMBO PERMIT #T05CM01810
AND FINALED ON 1-6-06
(2) UNITS A&B,-VIOLATION NOTABATED, SCHEDULED FOR REMOVAL
(3) UNITS A&B-VIOLATION ABATED, NEW FLAPPERS ISTALLED
(4) UNIT A-VIOLATION ABETED, NEW LAVE SINK INSTALLED ACCESS PNEL NOT REQUIRED.
(5) UNIT B-VIOLATION ABATED NEW FAUCET INSTALLED AT SINK
UNIT B VIOLATION UNABATED, LACKS SHOWER, DRAIN COVER AND ESCUTCHOU PLATES.
UNITS B&C VIOLATION ABATED, UNAPPROVED WATER LINE REPLACED WITH APPROVED COPPER LINE AND FINALED UNDER COMBO PERMIT T05CM01810 ON 1-6-06
(5) TC16-11 (D) MECHANICAL EQUIPMENT
VIOLATIONNOT ABATED-SCHEDULE TO BE REPLACED
(6) TC16-11 (F) INTERIOR SUFACES AND FEATURES (3) UNIT A
(1) VIOLATION ABATED-NEW FLOORING THROUGH OUT INTERIOR
(2) VIOLATION ABATED-BATHROOM WALLS REPAIRED AND REFINISHED
(3) VIOLATION ABATED- LAUNDRY ROOM CEILING REPAIRED, NEW ROOFING INSTALLED THROUGH OUT COMPLEX.
(7) TC16-11 J ACCESS CONTROL-UNIT B
VIOLATION ABATED-NEW WINDOWS INSTALLED
(8) TC16-12-BUILDING AND STRUCTURES EXTERIORS A 1&2
UNITA A VIOLATION ABATED ALL NEW WINDOWS INSTALLED
UNIT A,B&C VIOLATIONS ABATED-NEW WEATHER STRIPPING AND THRESHOLDS INSTALLED
UNITS VIOLATIO ABATED ALL NEW WOOD FASEIA INSTALLED, INSTALLED DETERIORED WOOD FREMES HAOUSE BEEN REMOVED STORAGE SHED-NEW SIDING AND PAINT
(9) TC16-12 BUILDING AND STRUCTURE INTEROR (B) FONDATION, WALLS ANS ROOFS (2&3) UNITS A,B&C-VIOLATIONS ABATED AII3 STRUCTURES EXTERIOR WALL HOUSE BEEN RENOVATED-NEW PAINT.
(10) TC16-12 BUILDING AND STRUCTURES EXTERIOR C PORCHES TC16-4 PERMITS REQ. UNITS A&B VIOLATION ABATED-PORCHES INVIOLATIONS HAVE BEEN REMOVED
(11) TC 16-12 BUILDING AND STRUCTURES EXTERIOR D COOLERS
UNITS A&B-VIOLATION NOT ABATED-NEW INSTALLED OF COOLER SCHEDULED FOR NEXT MONTH.
OWNER HAS MADE GOOD PROGRESS, ABATEMENT IS APPROX 90% ALL VIOLATION, SHOULD BE COMPLED WITH IN 2 WEEKS WILL EXTRACT 30 DAY TO ABATED REMAINIGN VIOLATIONS. PICTURES WERE TAKEN.
07/07/2005 INSP - INITIAL CODE ENFORCMENT Approved VISITED SITE, WALKED PROPERTY TO ACCESS PROGESS ON VIOLATION ISSED BY DNR UINTS 19 A,B,C, HAVE BEEN PAINTED, NEW WINDOW INSTALED (SAME FOR SAME) UINT 19 A HAZARDOUS PORCH STRUCTURE HAS BEEN REMOVED OVER HANG AT EASTSIDE HAS BEEN REPAIRED, PAINTED. NEW ELECTRICAL UP-GRADE FOR 19 A, B, & C HAS BEEN COMPLETED UNIT 19C IS CURRENTLY VACANT & SECURED AT THIS TIME. UNIT 17- EXTERIOR SURFACE HAS BEEN REPAIRED & PAINTED NEW WINDOWS INSTALLED (SAME AS SAME) NEW HOT WATER HEATER ENCLOSURE & PLUMBING HAS BEEN CORRECTED FOR HOT WATER HEATER. VENT STILL LACKING ON EAST SIDE OF UNIT. UNIT 15 C IS CURRENTLY BEING REHAB, NEW HOT WATER HEATER INSTALLED W/ ENCLOSURE, WASH BASIN IN VIOLATION HAS BEEN REMOVED. NEW WINDOWS INSTALLED (SAME FOR SAME)
UNIT 19 B & C DETERIORATED 7 DELAPIDATED PORCH STRUCTURE HAS BEEN REMOVED. MAJORITY OF TERMITE INFESTED WOOD TRIM HAS BEEN REMOVED & REPLACED WITH NEW WOOD TRIM. OWNER MAKING GOOD PROGRESS ABATEMENT IME WILL BE EXTENDED 45 DAYS. PICTURES WERE TAKEN.
01/13/2005 INSP - INITIAL CODE ENFORCMENT Correction Required 19 W. LINCOLN ST - APT A
ELECTRICAL:
(1) HAZARDOUS ELECTRICAL, SEVERAL ELECTRICAL CONDUCTORS HAVE BENN STRUNG OUT IN PORCH AREA & CONTAIN ILLEGAL SPLICES. EXTERIOR RECEPTACLE HAS NO POWER & LACKING WEATHER PROTECTION.
(2) 220 RECEPTACLE BY COOLER STAND IS DEAD & WILL BE REQUIRED TO REMOVE CIRCUIT.
(3) ILLEGAL SPLICED CORDS FOR WALL FURNACE & AC WALL UNIT.
(4) STRUCTURE HAS SEVERAL RECEPTACLES.
(5) BATHROOM LIGHT FIXTURE HAS NON GROUNDED RECEPTACLE.
(6) RECEPTACLE IN LAUNDRY ROOM IS DEAD & WILL REQUIRE REMOVAL FOR AC UNIT.
(7) BROKEN LIGHT SWITCH COVER PLATE IN LAUNDRY.
PLUMBING:
(1) ADDITION OF GAS PIPINE, CHECK FOR PERMITS.
(2) TOILET TANK FLAPPER LEAKING & LAVE SINK FAUCET LEAKING.
(3) WASHING MACHINE DRAINING INTO VENT PIPE - NO P-TRAP.
STRUCTURAL
1. HAZARDOUS PORCH STRUCTURE, STRUCTURE HAS BEEN BUILT WITHOUT PROPER ATTACHING HARDWARE AND USE OF 2 X 4 SPANNING OVER 4 FEET, ALL BOARDS ARE TOE NAILED. 4' X 4' POST HAVE BEEN NOTCHED MORE THAN A 3RD.
2. EAST SIDE OVERHANG HAS 3 FEET BY 2 FEET SECTION OF DRYWALL MISSING APPREARS SECTION HAS FALLEN OFF.
HEATING
1. FURNACE IN LAUNDRYROOM APPEARS TO BE ORIGINAL AND NO LONGER IN USE, APPEARS ROOM WAS SEPERATED AND CLOSET WAS BOOTED IN.
COOLER
COOLER STAND IS NOT MADE OF APPROVED MATERIALS AND HAS NOT BEEN MAINTAINED. FRAME WORK IS 2 X 4 LUMBER AND IS LACKING PAINT.
WEATHERPROOFING
1. BROKEN WINDOW AT WESTSIDE AND EASTSIDE (2).
2. WOOD FACSIA LACKING WEATHER PROTECTION PAIN COVERING AND BOARDS ARE IN A DETERIORATED STATE, CRACKED AND SPLITTING.
INTERIOR FEATURES
1. FLOORING IN BEDROOM IS CRACKED AND BROKEN, SEVERAL PIECES ARE IN A DTERIORATED STATE.
2. BATHROOM WALL HAS SIGNS OF DETERIORATION HAS BEGUN TO CRUMBLE.
3. LAUNDRY ROOM CEILING HAS WATER DAMAGE.
ACCESS CONTROL
1. WINDOWS ARE PAINTED SHUT AND SEVERAL WINDOW CRANKS MECHANISMS ARE NOT WORKING CORRECTLY.
FIRE SAFETY
1. NO WORKING SMOKE DETECTORS.
UNIT C
STRUCTURAL
1. NORTH WINDOW HAS BEEN ALTERED SMALLER WINDOW HAS BEEN INSTALLED.
EXTERIOR SURFACES
1. EXTERIOR SURFACE LACKING PAINT PROTECTION, SURFACE ARE CHIPPING OFF AND PEELING EXPOSED SURFACE.
POSSIBLE ZONING VIOLATION -WEST PROPERTY IS WITHIN 3 FEET OF PROPERTY LINE.
PLUMBING
1. NEWER COPPER LINES HAVE BEEN ADDED AND IS LACKING WEATHER PROTECTION AND NEED TO BE SECURED TO WALL.
ELECTRICAL SYSTEMS
1. MAIN SERVICE IN A DETERIORATED AND DILAPIDATED STATE/OLDER TYPE 60 AMP SERVICE IS RUSTED AND LACKS WEATHER PROTECTION.
2. INTERIOR RECEPTACLE COVER PLATE IS BROKEN.
3. UNDERGROUNDED BATHROOM LIGHT FIXTURE
4. 3 PRONG RECEPTACLE INSTALLED IN 2 WIRE SYSTEM
WEATHER PROTECTION
1. STORAGE SHED LACKING WEATHER PROTECTIVE PAINT COATING.
2. ENTRY DOOR LACKING WEATHER PROTECTION (WATHER STRIPPING).
HEATING
1. WALL FURNACE LACKING APPROVED GAS VALVE SHUT OFF.